一種雷電感應過電壓的快速算法及其精度檢驗
作者:
作者單位:

作者簡介:

通訊作者:

中圖分類號:

基金項目:

家重點研發計劃(2018YFC1507604)、國家自然科學基金項目(42075139, 41305138)、中國博士后基金資助項目(2017M621700)資助


A Fast Algorithm for Lightning-Induced Voltages and Its Accuracy Validation
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 圖/表
  • |
  • 訪問統計
  • |
  • 參考文獻
  • |
  • 相似文獻
  • |
  • 引證文獻
  • |
  • 資源附件
  • |
  • 文章評論
    摘要:

    本文基于B-P方程、Rusck方程和Agrwal耦合模型,開發出一種架空線雷電感應過電壓的時域快速算法。利用該算法研究了不同參數對雷電感應過電壓的影響,并利用2-D FDTD算法對其計算精度進行全面檢驗。結果表明:①首次回擊電流產生的感應過電壓的峰值較大,波頭陡度?。焕^后回擊電流產生的感應過電壓的峰值較小,而波頭陡度更大。②地面電導率 σ 對感應過電壓的幅值和極性影響較大。架空線路中點處的感應過電壓峰值與地面電導率呈負相關,而端點處的感應過電壓峰值與地面電導率呈正相關,并且在電導率較低(σ=0.001 S/m)時波形表現出雙極性特征。③架空線路中點和端點處的感應過電壓峰值均隨線路高度h增大而增大。④在閃電通道50~1000 m范圍內,本文算法模擬出的感應過電壓波形與2-D FDTD的結果基本一致,且峰值計算誤差均小于5%。綜上,由于本文算法計算時間僅需10 s并具有較高的計算精度,有利于在防雷工程中推廣應用。

    Abstract:

    Based on the B-P formula, Rusck formula and the Agrawal coupling model, we developed a time-domain method for lightning-induced voltages in overhead lines. Using this method, we studied the effects of different parameters on lightning-induced voltages and validated its accuracy using the 2-D FDTD method. The results show that: (1) The induced overvoltage generated by the first return current had a larger peak value and smaller wave head steepness. However, the induced overvoltage generated by the subsequent return current had a smaller peak value and larger wave head steepness. (2) Ground conductivity greatly influenced the amplitude and polarity of induced overvoltage. The peak value of induced overvoltage at the line centre negatively was correlated with ground conductivity. However, at the line end, the peak value of induced overvoltage positively was correlated with ground conductivity, and the waveform showed bipolar characteristics at poor ground conductivity condition (σ=0.001 S/m). (3) Both at the line centre and ends, the peak value of induced overvoltage increased with the line height. (4) Within distances from 50 to 1000 m from the lightning channel, the voltage waveforms calculated by our method were consistent with the 2-D FDTD results and the calculation error was less than 5%. In conclusion, because the calculation time of our method only needs 10 s with high calculation precision, it is very beneficial to be applied in lightning protection engineering.

    參考文獻
    相似文獻
    引證文獻
引用本文

張亮,李騫,石漢青.一種雷電感應過電壓的快速算法及其精度檢驗[J].氣象科技,2022,50(1):129~138

復制
分享
文章指標
  • 點擊次數:
  • 下載次數:
  • HTML閱讀次數:
  • 引用次數:
歷史
  • 收稿日期:2021-01-21
  • 定稿日期:2021-10-22
  • 錄用日期:
  • 在線發布日期: 2022-02-28
  • 出版日期: 2022-02-28
您是第位訪問者
技術支持:北京勤云科技發展有限公司
午夜欧美大片免费观看,欧美激情综合五月色丁香,亚洲日本在线视频观看,午夜精品福利在线
>