Measuring of Grounding Impedance of Power Plants and Substations
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 圖/表
  • |
  • 訪問統計
  • |
  • 參考文獻
  • |
  • 相似文獻
  • |
  • 引證文獻
  • |
  • 資源附件
  • |
  • 文章評論
    摘要:

    防雷接地網作為發變電站交直流設備接地及防雷保護接地,對保障生產安全運行起著重要的作用。發變電站接地網的測量結果存在接地阻抗值超標、感性分量過大的問題。通過仿真計算和實測對接地網測試中的感性分量對比分析,結果表明:接地阻抗的感性分量隨著電流引線與電壓引線之間距離增大而減小,通常不會大于阻性分量。過大的感性分量是由測試引線互感引起。基于此,給出了剔除互感阻抗的測量與計算方法,為接地網阻值的科學測試提供理論依據。

    Abstract:

    As the grounding of AC and DC equipment and lightning protection equipment, grounding grids play an important role in ensuring the safety of production operation. Measurement results of several plants show that the grounding impedances are all beyond the standard values, and that the inductive component is too big. A comparative analysis between theoretical simulation and measured results of the inductive component of grounding impedance shows that inductive component, which is generally no greater than resistive component, decreases with the increasing distance between current lead and voltage lead, and that excessive inductive component is caused by mutual induction. Based on the above, a method for calculating and eliminating the mutual inductance between the lead wires is brought out, which lays a foundation for reaching the exact grounding impedance.

    參考文獻
    相似文獻
    引證文獻
引用本文

史鋒旗,李貴玲,楊敏,李小龍.發變電站防雷接地阻抗測量分析[J].氣象科技,2016,44(3):489~494